Manuals Requests:

Here you can request any electrical, electronic, or instrumentation instruction / insatallation or operation  manual for any device you want.

Transformers- Transmitters- switches- Breakers- transmitters  etc for any company
 Cummins Siemens ABB Ykogawa General Elctric ABB Westinghouse  Foxboro.. etc


i have many gigabits of data.

Just Comment with your request and your email.and i will send you the manual you want

or send mail to : em17116@gmail.com

or facebook page https://www.facebook.com/pages/Electrical-Photos/393283367410736

8 comments:

Unknown said...

ask for any manual you want and i will send a link to download it

Anonymous said...

I am looking for the following information

Voltage Ur (kV)
BIL Up (kVp)
Rated Current Ir(A)
Rated Short Circuit Breaking Current Isc (kA)
Rated Short Circuit Making Current
Ima (kAp)
Rated Short Time Withstand Current (Momentary Current) (Ik) kA
Rated Duration of Short Circuit
tk (s)

for the reclosers below
A) Type RV-McGraw-Edison
B) Kyle Recloser Type V4E - Cooper
C) Kyle Recloser Type KFVME - Cooper
D) Kyle Recloser Type KFME - Cooper
E) Type VERSAVACII-Joslyn Hi-Voltage Corporation
F) Reyrolle - England

I would appreciate it if you can send me the manuals with those data.

My e-mail adress are AprilAC@eskom.co.za

Unknown said...

DEAR SIR,
TO AVOID MAJOR FAILURE WHAT IS THE MAINTENANCE/TESTING REQUESTED ON CCVT/CVT.
PLEASE KINDLY FORWARD.

Unknown said...

dear sir,

please furnish the recomended maintenance / testing on service ccvt/cvt.

Unknown said...

hey Govindan Palanichamy,
here alot of basic service that should be done from time to other.

- CAUTION: BEFORE PERFORMING ANY TESTS ENSURE THAT UNIT HAS BEEN COMPLETELY DE-ENERGIZE

- confirm of Volt tap ground switch up all the time.
- Megger X and Y windings to tank should read 50 meg ohms or more. every while.
- Megger P2 to tank should read 50 meg ohms or more.
- Measure resistance from P2 connection to tank, should read less than 1000 ohms.
- Measure capacitance between CAR connection and basebox. This gives C2 value.
- Measure capacitance from top of capacitor to basebox. This gives C1 value.
- Measure P1 - P2, should read less than 75 ohms
- Check all connections Daily.
- Check harmonic suppression filter wiring and components, replace as necessary.
- Check for leaks around tank
- Check expansion chamber on top of lower capacitor unit

Unknown said...

perform a regular
visual inspection of the following:
• Chipped porcelain
• Abnormal pollution accumulation
• Oil leaks
• Check oil level of the basebox by means of the oil
gauge.

Anonymous said...

I want to read turbine speed control by automatic governor chapter-5 please send to my mail id mahesh.petro15@gmail.com

trymorechaga said...

I am looking for the maintenance manual for Mindray Anaesthetic machine
my email is : trychaga@gmail.com